Wayfinding in Heavy Smoke:
Decisive Factors and Safety Products
Findings Related to Full Scale Tests
Geir Jensen
IGP AS
(merging to become InterConsult Group - ICG, 1 May 1998)
(All related figures to this article can be found here. The
illustration will open in a separate browser window).
Abstract
This paper presents a summary of a series of four reports on safe
evacuation from smoke. The first report is a literature study on the subject. The next
reports on a full scale test series and the third makes a discussion of the decisive
factors involved in safe escape from smoke. The fourth report presents a way of
calculating visibility in smoke. The focus is on the safety of individuals wearing no eye
or breathing protection, on wayguidance marking, on human behavior and on visibility in
smoke. Also, relations to the time humans may endure in severe smoke and to the travel
distances involved, are considered.
The results are generic to public buildings or industries where there may
be a possibility of several safety measures failing, including power failure and smoke
blocking normal lighting, thus exposing individuals to extreme difficulties in navigating
to a safe haven - be it a protected room or the outside of a structure.
Being able to navigate and cope with short periods of exposure to severe
smoke may be crucial in saving ones life, or even in performing vital operations such as
shutdown procedures in order to save others.
The paper attempts to submit an overview of available safety products for
way guidance in smoke of which 7 system categories were tested in full scale involving 84
human subjects. Test smoke conditions varied within optical smoke densities of OD 1.0/m
and 1.5/m. 6 blind persons took part in the tests and made it possible to test the
performance of tactile marking systems in 'total darkness' as well. One outstanding
conclusion is that the visibility distance, not the luminance, is the most important
factor of visibility in extreme smoke. This makes low luminance afterglowing line marking
outperform electrically powered point sources of light.
Introduction
Emergency lighting and signage do not perform as expected at fire
disasters. Very often systems are found to be nonoperative, not providing useful
wayguidance or both. There are two common denominators: the systems are traditionally not
required to be designed for smoky conditions and they are prone to failure by lack
of maintenance or complexity.
By study of fire disasters /3/ it is clear that to increase fire safety
substantially one may design wayguidance for smoke.
Seven different concepts of Emergency Egress Information Systems also
referred to as wayfinding or guidance systems, were tested with human
subjects. Concepts included visual and tactile, powered and nonpowered, systems /4/.
It was decided to review statistics of fire disasters and research
experience in order to assess how far and for how long evacuees are capable of moving in
fire until they are put out of action by the smoke /5/.
A method of calculating the visibility in a smoke was developed /6/.
Optimal locations of wayguidance marking were determined /5/. Evacuation aided by audible
information - informative voice messages - and smoke hoods, were also briefly dealt with
/4/, but is not included in this paper.
Vital implications of safe evacuation in smoke
Limits of human endurance in exposure to smoke
Many researchers have suggested endurance limits in smoke /4/. A set of
simple critical limits for human exposure to effects of fire were deduced: Temperature
limit: 150 oC. Limit of visibility without wayfinding system ('turn back'
limit): 5 m. Accumulated/dose CO: 30 000 ppm min. Synergy effects of one or more factors
override these limits in a given fire. Reduction of visibility and the presence of CO are
the prime risk factors when evacuating in smoke /3,4/.
The
smoke severity to which wayfinding systems must perform
Instead of awaiting a full understanding of the synergetic effects of
smoke on humans by smell, visibility, stress, toxicity etc some researchers have linked
both incapacitation, survivability, tenability and 'turn back' limits to specific smoke
density levels. This optical density concept were adapted for the wayfinding
classification presented in this paper.
It appears from reports on catastrophes that a lot of people survive smoke
that obviously exceed both the short term incapacitation and the survivability limits.
While people will turn back at OD 0.25/m (no wayguidance) some people have apparently
survived moving through smoke densities between OD 2/m and OD 10/m.
Statistically, those who survived smoke in fire catastrophes moved on
average only 9.1 m in smoke. Only 10% moved through smoke more than 16 m. This equals time
exposures substantially shorter than 1 min, while survivability thresholds
typically are defined by 1 minute exposure. This may explain why people survive smoke
densities exceeding 'survivability limits' like that of OD 1.64/m proposed by Gross /4/.
Importance of wayfinding
Very small margins have meant the difference between life and death in
actual disaster situations. A few more meters, a few seconds less, choosing the right
direction at just one junction, just a little less smoke or slightly better visibility,
and lives could have been saved. This became clear from the literature study of fire
disasters.
Some issues discussed in /5/ were:
how
far and for long can a person move in the smoke we may encounter in potential fire
disasters?
what
dosages of toxins (dosages are a function of time and concentration) affect persons during
evacuations?
· how much smaller will these dosages be if evacuation times are reduced?
· how long do escape hoods need to function in critically dense smoke in
order to provide sufficient protection?
Even though research is scarce, it is quite clear that small improvements
in visibility or reduction in smoke irritation may save many lives at multiple life fire
risks. It is a fact that in fires, people remain too long in the smoke and consume
excessive dosages of CO because they cannot find their way out. The most important factors
that make people turn back or give up trying to escape are poor visibility and irritation
of the eyes by smoke. The next most important is that smoke also irritate the respiratory
system.
Serious smoke intoxication or the effects of heat are thus not the prime
factors that stop the progress of evacuees. The fact that post-mortem reports describe
respiratory damage and toxic compounds in the blood is of course a consequence of the
environment at the time just before death rather than at the time the deceased stopped
progressing or turned back. The reason evacuees stop or turn back may be poor visibility,
irritation of the eyes, heat or a combination of factors. We find it reasonable to suppose
that some time pass before the deceased meets high concentrations of CO and remains in
them so long that he or she is incapacitated. After fainting or anesthesia, some time also
pass before death occurs.
On board the Scandinavian Star the catastrophic fire developed in the
evacuation route and the volume in which smoke could disperse was limited. For this reason
the smoke was more dense than in any of the other disasters we considered. At the World
Trade Center incident no one died despite several hours exposure to smoke as the toxic
fumes became diluted throughout a large volume.
Travel distance in severe smoke
Toxins in the Scandinavian Star put people out of action after only 30
seconds (researchers guesstimate), corresponding to a walking distance of about 15 meters.
During real-life evacuations, statistical data show that 90 per cent of survivors moved
less than 16 meters in smoke. The smoke varied from light to extremely dense (optical
density (OD) from 0.1/m up to 1.0/m). This suggest time available is about 50 seconds in
severe smoke given a mean travel speed of 0.35 m/s.
Thus, given a good wayfinding system or a familiar route, the life saving
potential is very substantial indeed. Class I wayfinding systems (definitions below) are
called for, and/or escape hoods etc to protect eyes and respiratory system.
A wayfinding system is to no avail if people die on their way out, nor do
escape hoods if they do not find the exit. A combination of these two measures is even
better since they complement each other.
Walking speed
Careful studying has indicated a level of smoke severity and time of
exposure (irritant smoke at density 1.53 to 2.26/m, exposure time 3 to 4 min, escape path
25 to 30 m) as the limit to what normal people will endure without protection - no matter
what emergency egress information system is being used.
Speeds were within 0.2 to 0.5 m/s which appears to be the "ultimate
speed in heavy smoke conditions", independent of the type of wayfinding system
applied.
Importance of visibility in emergency operations
At industry plants, underground installations and complex high risk
structures such as nuclear power plants or offshore drilling platforms visibility may
become crucial in severe smoke. In order to perform shutdowns, extinguish fires,
closing valves, rescue work or other intervening operations at imminent disaster, or
indeed when all things have failed, personnel may encounter very dense smoke, if ever so
briefly.
Normal and emergency lighting systems are easily blocked by smoke and may
create total darkness or very dense foglike atmosphere reducing visibility to less than 2
m. Lighting systems often fail when subjected to structural damage, power shutdowns etc,
in fire or other incidents. Most important are reliability as well as visibility
at close range.
Visibility in smoke
The results of the tests showed that wayfinding systems performed very
differently, and in many respects not according to expectations. Our mathematical
calculations of visibility in smoke have been compared and verified by the tests. The
method of calculation can be used to estimate if a given wayfinding system is suitable for
a given smoke density, and we consider this the first available method to offer this
degree of accuracy /6/.
We have made visibility diagrams for luminances from 0.0025 to 320 cd/m2,
as a function of percentage light-loss per meter and distance. The luminance of adaptation
varied from 0.001 to 1 cd/m2 /6/.
Viewing distance, not power or luminance, is the crucial factor at high
smoke density. This relies not on obscuration by distance alone, but on the simple reason
that visibility of any luminance must converge to zero at 100% obscuration.
Normal lighting, or indeed emergency lighting and any lighting that does
not contribute to guide evacuees, will only distract and reduce visibility and readability
of signs and information relevant to successful escape in smoke.
The photoluminescent strip built into the directional rail in test was 25
mm wide only, and tilted to an angle of only 30o to the view direction.
Amazingly, this design performed well even at smoke densities between OD 1.4/m and 1.5/m,
but is explained by the short eye-to-object distance according to the above /4/.
The distinct green system offered the best visualized readable
information of the systems tested, with black letters and arrows on direction and
distance. But as with any system of point sources of light it becomes impractical to space
the points close enough for smoke more dense than approximately 1.5 /m optical density
/4/.
Test method for way guidance system visibility performance in smoke
Based on the experience /4/ a test method for determining visibility
performance of visual way guidance systems in smoke has been proposed to working group 3B
of technical committee 169 on European standard CEN /10/. Way guidance systems may be
tested up to OD 2/m. The method does not apply to tactile systems but to any visual system
- photoluminescent or powered. Preliminary tests are yet to be done.
Calculated and observed visibility performance
We recognized the need for tools that would enable us to select the most
suitable wayfinding system for any given case. Such a tool is the set of nomograms of the
relationships between smoke density, visibility, distance to visual markings, lighting
parameters and the physical requirements of the eye, which we have developed and presented
in /6/.
Previously published calculations made by Jin and Yamada /1,2/ were based
on the visibility of conventional wayfinding systems when normal lighting was on.
The method of calculation was internationally criticized because it failed to take into
account the sensitivity of the eye to different angles of vision, and because it did not
employ luminance values that are relevant to improved wayfinding systems.
Our calculations take the sensitivity of the eye into account. All
available research results on evacuation in smoke show that when normal lighting is
switched on, visibility is very much reduced. Our numerical tools allow calculations to be
made without normal lighting, and employing relevant luminances. As well as being a
practical tool, the systematic calculations offer a better physical and physiological
understanding of visibility conditions in smoke. These calculations can thus help to
further develop existing wayfinding systems or to develop new systems.
Wayfinding information
Researchers have insisted that wayfinding systems should include
information on direction and distance to nearest exit. The test supported
this view. Such information proved effective and two participating manufacturers promptly
changed their policy. Wayfinding information is discussed further in Norwegian reports not
referenced in this paper.
Location of marking and walking behaviour in smoke
In large building complexes, where the risk of a fire catastrophe prevail,
one should prepare for a fast escape in upright or forward bent walking mode, rather than
undue crawling that may possibly cause congestions and chaos, or worse: excessive time
exposure to lethal smoke.
Following the research we recommend continuous marking at low
location, i.e. below approximately 1000 mm height, and clearly visual signs above the exit
doors. An optimum system design would be continuous marking at waist height, at skirting
board or at the floor center line.
The recommendations are based on all conditions of visibility: Normal,
smoke, blackout, normal and smoke as well as blackout and smoke.
Reliability
Powered (back-lit) lighting offer better readability of signs. But the
higher luminance of powered systems compared to photoluminescent is marginal in dense
smoke and do not justify implications of cost, reliability and aesthetics involved.
Photoluminescent or/and tactile systems were found to have superior
reliability due to the inherent simplicity, and also most reliable in terms of visual
information, provided they are designed to be continuous.
Way guidance system categories
A simple classification - Classification of Emergency Egress
Information Systems Designed to Perform in Smoke - is introduced, dividing guiding
systems in two classes by limits of optical density. Class I means smoke density exceeding
OD 1.5/m, while class II is only up to OD 1.5/m.
To clarify: optical smoke density OD of 1.5/m is approximately equal to a
visibility distance of 0.6 meter to forward illuminated objects, such as a hand
outstretched, and of 1.5 meter to rearward illuminated (back-lit) sources of light.
Conventional emergency lighting signs do not qualify in either class
because the spacing of light sources exceed the required viewing distance. All seven
concepts tested and designed to perform in smoke will do as Class II systems, but
some only if modified.
The superior overall system tested is a patented safety rail system: the
only system tested to Class I. This nonpowered system combining visual and tactile
information is a hand rail featuring directional notches and (optional) photoluminescent
marking. As explained, however, even pure photoluminescent systems may be designed to
Class I.
Wayfinding system
Class |
Smoke density
OD (m-1) |
Visibility distance
(m) |
Wayfinding system design alternatives |
Type of building structure |
|
|
Rearward illuminated |
Forward illuminated |
(those designed for Class I also comply to Class II or No
smoke) |
|
I |
> 1.5
1.5 |
< 1.5 |
< 0.6 |
Tactile, directional handrail.
Visual handrails. |
Large, complex public structures
Complex industry structures.
Underground structures.
Other high risk areas/structures. |
II |
0.1-1.5 |
1.5-25 |
0.6-10 |
Continuous low location marking |
Public buildings, offices, hotels |
No smoke |
< 0.1 |
> 25 |
> 10 |
Point sources of light - 'conventional escape route marking' |
Small, low risk public structures.
Residences, workplaces, schools etc where one is familiar. |
Performance of way guidance systems
Based on results of the full scale test and literature study the following
comments were made on the potential suitability of different way guidance systems:
Spaced point sources of light (conventional emergency lighting)
These systems are generally not intended for smoky conditions. At typical
spacing worldwide allowing viewing distances up to 30 m they may only be useful in smoke
densities less than OD 0.1/m. Spacing less than 7 m (3.5 m viewing distance) should not be
practical, as continuous visual systems then will be preferred. A 7 m spacing could do up
to a smoke density of approximately OD 0.8-1/m. Systems based on space point sources do
not conform to any class within the classification system proposed for wayfinding systems
in smoke.
Photoluminescent (floor proximity systems or floor center line systems)
Improvement potential is considered significant if the material on
skirting boards or wall (proximity systems) become more perpendicular angled towards
upright walking persons, and located higher from the floor. Black should be preferred to
green letters.
Floor center line systems: As the viewing distance is fixed improvements
must rely either on higher luminance or larger arrows designed in photoluminescent
material or both. The system may be complemented by some signage high above the floor, at
strategic points such as rails and handles.
Photoluminescent continuous marking offered the best potential of the
concepts in the test in terms of visibility, reliability and costeffectiveness. Design
improvements can be achieved by locating the strip closer to the eye of evacuees, and to a
lesser extent also by increasing the excitation, the luminance and/or width of the strips.
The systems have a large unexploited potential if the research results are implemented.
The functional reliability is a definite asset as well as the very long operational times
(exceeded 8 hours at time of test, new systems improved), the no glare effect, the
unanimous delineated marking and the low cost and maintenance involved.
Floor proximity powered (back-lit) strip
A proximity back-lit strip was not tested as intended /4/. We can only
assume that such a system would perform as well as the two continuous photoluminescent
systems, and possibly even close to the performance of the distinct green semicontinuous
system. A directional information element of the system would be required in any
case.
Floor proximity semicontinuous distinct green
A system of semicontinuous (closely spaced point) sources of cold cathode
tube light fixtures were tested. This patented system provide a distinct green light of
high performance in smoke. Applied at the skirting-boards and spaced by 4 m, however, it
only scarcely suffice to Class II requirement. Substantial improvement could be done if
the system was continuous. As a further improvement the light tubes may be lifted
to waist height to decrease viewing distance.
Directional rail
The Safety Rail System is a patented hand rail of directional notches so
that anyone, in total darkness or blind, and independent of electric power, may sense by
hand the escape route and direction. The embedded photoluminescent strip as in one tested
version should be tilted, and/or the luminance and/or width of the strip should be
slightly increased. It is vital that the tactile rail also incorporate a continuous visual
line signage to prevent undue clinging to the rail.
Limitations
It should be observed that the full scale tests were performed with the
general lighting turned off, and that the subjects entered the dark (except for visual
marking) and smokefilled route with eye adaptation to approximately 150 lux. The route did
not provide open spaces in excess of 15-20 m2 or any straight lengths in excess
of 8 m. The subjects wore closed circuit breathing apparatus for use in an emergency (mask
used only in the real smoke tests) that prevented them from bending or crawling - this
made test parameters uniform but disfavoured the low luminance low location systems.
The tested photoluminescent systems were all based on zinc sulfide.
Current systems are being manufactured with new earth-borne pigments that provide a level
of luminance several times higher.
Conclusions
A decisive factor to evacuees is the time they become exposed to heavy
smoke. This time is governed by the perceived wayguidance of the evacuees - less by the
length of the smoke filled escape route, which is within 16 m only in 90% of fire
disasters by statistics - therefore wayfinding systems for smoky conditions play an
important role.
One need to design for wayfinding in smoke exceeding OD 1.5/m in some
industry as well as some public structures, contrary to current proposed general limits of
OD 0.4/m within some international standardization bodies.
Very high performance of guiding people in smoke may be provided by simple
nonpowered wayfinding systems: a tactile safety hand rail system or
photoluminescent marking or both. Decisive factors in designing optimum wayfinding systems
for smoky conditions are continuous marking less than 1meter above floor level,
simplicity, independence of electric power, long operational times, simple maintenance and
low cost.
Viewing distance, not power or luminance, is the crucial factor at high
smoke density. This relies not on obscuration by distance alone, but on the simple reason
that visibility of any luminance must converge to zero at 100% obscuration.
A photoluminescent strip at 0.5 m distance to the eye is more visible than
the most powerful luminaries at just 1.5 m.
Without respiratory protection the time available in severe smoke is
approximately 50 seconds at a mean travel speed of 0.35 m/s. This is relevant to the 16 m
length of escape in smoke which accounts for 90% of incidents. Thus, given a good
wayfinding system or a familiar route the life saving potential is very substantial. This
calls for Class I wayfinding systems, and/or escape hoods etc to prevent irritation of
eyes and respiratory system. A wayfinding system is to no avail if people die on their way
out, nor do escape hoods if they we do not find the exit. A combination of these two
measures is even better since they complement each other.
(All related figures to this article can be found here).
References
1 Jin and Yamada: Irritating Effects of Fire and Smoke on Visibility.
Fire Science and Techn. Vol. 5 No 1/85.
2 Jin, T.: Human Behaviour in Smoke, Proceedings of the 4th Joint Panel
Meeting, UJJNR Panel of Fire Research and Safety. Tokyo, p. 324, 1979.
3 Jensen, Geir: Fire Diasters - Better Fire Escape Methods. IGP AS.
1991.
4 Jensen, Geir: Evacuating in Smoke. IGP AS. 1993.
5 Jensen, Geir: Evacuating in Smoke - Decisive Factors. IGP AS
1994.
6 Nersveen, Johnny: A Method of Calculating Visibility in Smoke.
IGP AS. 1994
7 Jensen, Geir: Norwegian research shows usefulness to blind of
'notched rail' in fires. Fire. July 1993.
8 Meland, Ø, Jensen G: Evacutation in smoke. RINA International
Conference on Lifesaving at Sea. 1993.
9 Tuomisaari, Maarit: Visibility of exit signs and low-location lihting
in smoky conditions. Technical research center of Finland. 1997.
10 Heskestad, A., Jensen G: Test Method for Way Guidance Systems:
Visibility in Smoke. Proposal to CEN Standard TC 169 WG3B. IGP AS. 1997
|